Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Correction Required
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 05/22/2000 |
ELECTRIC - SERVICE UPGRADE |
|
Correction Required |
ADDTL COMMS - OK TO CLEAR BOND GAS PER N.E.C. ART. 250 |
| 05/22/2000 |
ELECTRIC - SERVICE UPGRADE |
|
Partial Approval |
IVRS - Inspection 0000* |