Permit: T00EL01208

Parcel: 12703525B


Addresses:

5601 E BAKER ST


Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Permit Number - T00EL01208

Inspection Description - ELECTRIC - CABLE DROP

Inspection Status - Approved

Date Description Inspector Results Comments
05/07/2001 ELECTRIC - CABLE DROP Approved IVRS - Inspection 0000*
04/13/2001 ELECTRIC - CABLE DROP Denied IVRS - Inspection 0245*1. INSTALL GROUNDING ELECTRODE SYSTEM PER ART. 250, 230 NEC. 2. GROULD 10 X 10 J-BOX.3. SUPPORT 1/2" EMT AT J-BOX 4.INSTALL PERMANENT ADDRESS LABEL SCREWED OR RIVITED TO SERVICE ENCLOSURE. 5.ALL CIRCUIT BREAKERS MUST BE MURRAY BRAND. 6.SEAL 2" KO"S IN BACK OF PANEL. 7. ANCHOR AT TOP OF RISER PULLING OUT OF PANEL.