Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
Permit Number - T00EL01199
Inspection Description - ELECTRIC - RECONNECT
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/18/2000 | ELECTRIC - RECONNECT | Approved | ||
05/24/2000 | ELECTRIC - RECONNECT | Correction Required | ADDTL COMMS - 1. PERMANENT METAL TAG IS REQUIRED AT EXTERIOR DISCONNECT PANEL A PANEL B 2. NEED PROPER SIZED BOND JUMPER FOR PANEL A RACEWAY (FOR 200 AMPS) AND TIGHTEN ALL LUGS. 3. NEED K.O. SEALS 4. ISOLATE PANEL A 5. NEED FIRE FINAL STEVE LING 791-5550 X147 MAJUTA X136 791-4591 FIRE PREVENTION. | |
05/24/2000 | ELECTRIC - RECONNECT | Partial Approval | IVRS - Inspection 0000* | |
05/18/2000 | ELECTRIC - RECONNECT | Correction Required | ADDTL COMMS - 1. IDENTIFY INTERIN SUB PANELS TO COINCIDE WITH EXTERIN DISCONNECTS 2. REMOVE ALL INTER-PANEL FEEDERS AT HALLWAY PANELS 3. DOUBLE LUGGING AT CENTER PANEL AND SPLICED IN SMALLER CONDUCTOR NOT RATED AT 200 AMPS PER FUSING 4. RE-DO PANELS AND FEEDER TO ORIGINAL STATE NEED NAME OF LICENCED L-11 CONTRACTOR BEFORE NEXT INSPECTION. | |
05/18/2000 | ELECTRIC - RECONNECT | Denied | DENIED |