Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date |
Description |
Inspector |
Results |
Comments |
| 08/18/2000 |
ELECTRIC - RECONNECT |
|
Approved |
|
| 05/24/2000 |
ELECTRIC - RECONNECT |
|
Correction Required |
ADDTL COMMS - 1. PERMANENT METAL TAG IS REQUIRED AT EXTERIOR DISCONNECT PANEL A PANEL B 2. NEED PROPER SIZED BOND JUMPER FOR PANEL A RACEWAY (FOR 200 AMPS) AND TIGHTEN ALL LUGS. 3. NEED K.O. SEALS 4. ISOLATE PANEL A 5. NEED FIRE FINAL STEVE LING 791-5550 X147 MAJUTA X136 791-4591 FIRE PREVENTION. |
| 05/24/2000 |
ELECTRIC - RECONNECT |
|
Partial Approval |
IVRS - Inspection 0000* |
| 05/18/2000 |
ELECTRIC - RECONNECT |
|
Correction Required |
ADDTL COMMS - 1. IDENTIFY INTERIN SUB PANELS TO COINCIDE WITH EXTERIN DISCONNECTS 2. REMOVE ALL INTER-PANEL FEEDERS AT HALLWAY PANELS 3. DOUBLE LUGGING AT CENTER PANEL AND SPLICED IN SMALLER CONDUCTOR NOT RATED AT 200 AMPS PER FUSING 4. RE-DO PANELS AND FEEDER TO ORIGINAL STATE NEED NAME OF LICENCED L-11 CONTRACTOR BEFORE NEXT INSPECTION. |
| 05/18/2000 |
ELECTRIC - RECONNECT |
|
Denied |
DENIED |