Inspection Status: Correction Required
Inspection History: ELECTRIC - RECONNECT
| Date |
Description |
Inspector |
Results |
Comments |
| 05/19/2000 |
ELECTRIC - RECONNECT |
|
Correction Required |
ADDTL COMMS - 1. NEED PERMIT AND APPROVED PLAN FOR NEW WALK/ ELECTRIC AND WALK IN FREEZER (NEW WALK AT S.E. CORNER) NEW FREEZER AT S.W. CORNER APPROVED PLAN TO SHOW 340 W AJO ENTIRELY WILL NEED BUILD EL MECH AND PLUMBING FINALS WILL NEED LICENSED CONTRATOR CALL 791-5550 AND LEAVE NAME L-11 ELECTRICAL BEFORE NEXT INSPECTION. |
| 05/19/2000 |
ELECTRIC - RECONNECT |
|
Denied |
IVRS - Inspection 0999* |
| 05/10/2000 |
ELECTRIC - RECONNECT |
|
Correction Required |
ADDTL COMMS - 1. SUB PANEL INSIDE COVER ALL UN USED CIRCUIT BREAKER SPACES, SEAL ALL OPEN HOLES ON ENCLOSURE 2. RECEPTACLE BELOW PANEL TO RIGHT TO HAVE HOLES SEALED AND COVER PUT ON. 3. OPEN WIRING IN LARGE J-BOX ABOVE PANEL AND SMALL J-BOX TO HAVE PROPER DEAD ENDS ON WIRES AND BOXES TO HAVE COVERS AND SEAL HOLES. 4. SEAL HOLE AT BOTTOM OF 30 AMP DISCONNECT WEST WALL 5. EXIT LIGHT FED FOR 344 AT SOUTH DOORS IS ON DISCONNECT AND FEED FROM 340 6. NEW WALLS AT SOUTH EAST END OF BUILDING NOT FINISHED NOR PERMITTED (A PERMIT WAS NEVER OBTAINED FOR THESE, YOU NEED TO FIRST OBTAINED AN L-11 ELECTRICIAN TO CLEAN UP ELECTRICAL PROBLEMS CALL 791-5550 EXT 136 TO ADVISE WHO IT WILL BE 2ND OBTAIN A PERMIT AT OUR OFFICE FOR UNFINISHED WALLS. |
| 05/10/2000 |
ELECTRIC - RECONNECT |
|
Denied |
IVRS - Inspection 0999* |