Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/11/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
| 01/09/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245* LUGS IN GUTTER AT ROOF TO CLOSE TO ENCLOSURE WALLS, INSTALL INSULATING MATERIAL BETWEEN BUSS, LUGS AND WALLS OF GUTTER, NEED TO VERIFY REVISED PLANS STAMPED BY CERTIFIED ENGINEER ELECTING ACTUAL INSTALLATIONS OF CONDUIT, FEEDER SIZES AND NUMBERS FIRE PROOF ALL CONDUIT PENATRATIONS BETWEEN FLOORS |