Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T00EL01031
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/19/2000 | ELECTRIC - FINAL | Approved | 10/19/00 BACK UP GENERATOR | |
06/06/2000 | ELECTRIC - FINAL | Correction Required | ADDTL COMMS - 1. IF SPLIT BOLT CONNECTOR USED TO CONNECT PER 250-32 USE CONNECTOR SIZED SMALL ER FOR THE (2) #4 BARE SEL.CU 2. POSITIVELY IDENTIFY NORMAL POWER BREAKER TO TRANS SWITCH 3. WILL NEED LISTING FOR THE GENERATOR OR LETTER(3RD PARTY CERTIFICATION) 4. DUCT WORK ABOVE NEW PANEL BOARD AND TRANSFER SWITCH IN VIOLATION OF CODE ANY OTHER METHODS TO BE STAMPED AT OFFICE. | |
06/06/2000 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* |