Permit: T00EL01031

Parcel: 11901042B


Addresses:

200 E BENSON HY


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T00EL01031

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/19/2000 ELECTRIC - FINAL Approved 10/19/00 BACK UP GENERATOR
06/06/2000 ELECTRIC - FINAL Correction Required ADDTL COMMS - 1. IF SPLIT BOLT CONNECTOR USED TO CONNECT PER 250-32 USE CONNECTOR SIZED SMALL ER FOR THE (2) #4 BARE SEL.CU 2. POSITIVELY IDENTIFY NORMAL POWER BREAKER TO TRANS SWITCH 3. WILL NEED LISTING FOR THE GENERATOR OR LETTER(3RD PARTY CERTIFICATION) 4. DUCT WORK ABOVE NEW PANEL BOARD AND TRANSFER SWITCH IN VIOLATION OF CODE ANY OTHER METHODS TO BE STAMPED AT OFFICE.
06/06/2000 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*