Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 10/04/2000 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
|
| 10/03/2000 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
DENIED MAIN BREAKER EXCEDER 6' - 7" A RE INSPECTION FEE IS DUE BEFORE THE NEXT INSPECTION |
| 05/09/2000 |
ELECTRIC - SERVICE UPGRADE |
|
Partial Approval |
IVRS - Inspection 0000* |
| 05/02/2000 |
ELECTRIC - SERVICE UPGRADE |
|
Correction Required |
ADDTL COMMS - 1. TREAT PLYWOOD TO WATER PROOF 2. NEED PERMANENT RAISE LETTER ADDRESS TAG PER CITY AMENDMENT DIRECTION. 3. HOSE BIB UNDER SERVICE NEEDS TO BE COMPLETLY REMOVED OR MOVE SERVICE. 4. 2 1/2 LOCK NUTS BACKWARDS AND NEED GROUNDING BUSHING AND BONDING JUMPER ON RISER. DO ALL OF THE ABOVE BEFORE THE NEXT INSPECTION. |
| 05/02/2000 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0999* |