Permit: T00EL00969

Parcel: 122081030


Addresses:

2205 N ISABEL BL

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/11/2000 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
OK TO CLEAR
10/05/2000 ELECTRIC - FINAL Denied 10/05/00 SMOKE DETECTOR MOUNTED TO LOW, SHOULD BE 6" TO 12" BELOW CEILING.
REMOVE OR INSTALL OLD ROMEX WIRING IN CONDUIT IN SOUTH WEST STORE ROOM
09/29/2000 ELECTRIC - FINAL Denied IVRS - Inspection 0245*
CONTRACTOR TOOK OFF W/JOB CARD AND PERMIT
NEW SERVICE I.D. CIRCUIT BREAKERS AND FILL IN BLANK KNOCK OUTS ON PANEL DEADFRONT
EXPOSE GROUND RODS
BOND GAS PIPING
APPEARS TO BE PVC AND METAL PIPE WATER SYSTEM
INSTALL SMOKE DETECTOR IN BEDROOM INSTALL COVERED LIGHT FIXTURE IN CLOSET, OPEN BULB TYPE NOT APPROVED
INSTALL 2-WIRE OUTLETS ON UNGROUNDED CIRCUITS OR GFI RECEPTACLE AHEAD OF CIRCUIT INSTALL MIDWEST COOLER BOX