Permit: T00EL00968

Parcel: 138100830


Addresses:

6066 S NOGALES HY


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T00EL00968

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/31/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*OCCUPANT TO OBTAIN PERMITS TO INSTALL AC UNITS, SINCE WORK HAS STARTED PLEASE DO THIS WITHIN 5 DAYS THEN THEIR WILL BE A FOLLOW UP.
04/04/2001 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000* OK TO CLEAR SERVICE CALL FOR FINAL WHEN COMPLETE
03/21/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999* 1) FEED SHOWS 800AMP ON PLAN WITH 400RCM FEEDERS SVS HAS 800 AMP MAIN ON PARALLEL 250 MCM AL= 230+230=460A MAIN SB 500 AMP 2) B-1 ON PLAN SHOWS 80 ACB ON 200AMP CB 3) PANEL A1 NEED TO INSTALL A JUMPER FROM UFER TO PIPE END. 4) TERMINATE GROUND IN A1 1/0 COPPER-WEST SIDE 5) B1 DAMP GROUND TO END OF PIPE REVISE PLANS PER LETTER
03/16/2001 ELECTRIC - FINAL Denied PLEASE HAVE PLANS AND EQUIPMENT OPEN. TIME IS VERY CRITICAL TODAY PLEASE RE CALL
03/02/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999* 1) DO NOT HAVE ANY VERIFICATION OF UFER SYSTEM BEING INSP. CAN SEE GAS BOND, HOW DOES WATER BOND GET TO WATER LINE? 2) INSP. DOES NOT HAVE TOOLS TO REMOVE SW GEAR COVER TO INSP. 3) HAVE ELEC. CONTRACTOR SET UP TIME TO MEET ON DAY OF INSP. WOULD LIKE TO INSP. ALL PANELS AND DISTRUBUTION SERVICE 4) FEEDERS CHANGED FROM 400MCM AL TO 300MCM. THIS NEEDS TO BE CHANGED ON THE PLANS BY ENGINEER AND APPROVED
03/01/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0925* PLAN NOT AVALIABLE