Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/15/2000 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* ELECTRIC PEDISTAL MUST BE RELOCATED TO PROVIDE PROVIDE PROPER CLEARANCES YOU CAN NOT SIMPLY CONNECT MULTIPLE EXTENSION CARDS AS A POWER SUPPLY SLOPPY WORK IN INTERIOR PANEL IMPROPER CONNECTIONS NEED SMOKE DETECTORS NEED TO INSTALL GFCI OUTLETS AROUND KITCHEN SINK HEATER NEEDS TO BE SERVICED WATER HEATER NEEDS TPRV DISCHARGE LINE WALLS AND CEILING OF WATER HEATER CLOSET NEED TO BE 1 HOUR FIRE RATED. EXHAUST VENT FROM WATER HEATER DOES NOT HAVE PROPER CLEARANCES ELECTRIC WIRING TO COOLER AND BEDROOM HAZARDOUS |
|
| 04/17/2000 | ELECTRIC - FINAL | Correction Required | ADDTL COMMS - SUPPORT SUB-PANEL FEEDING M.H. GROUND SYSTEM PER N.E.C. MUST HAVE APPROVED CONNECTION AND CORD LISTED FOR MOBILE HOME USE SUB-PANEL MISSING DEAD FRONT COVER. OWN NOT HOME, COULD NOT ACCESS INSIDE COULD NOT LOCATE METER | |
| 04/17/2000 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000* |