Permit: T00EL00904

Parcel: 11103021A

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
09/15/2000 ELECTRIC - FINAL Denied IVRS - Inspection 0999*
ELECTRIC PEDISTAL MUST BE RELOCATED TO PROVIDE PROVIDE PROPER CLEARANCES
YOU CAN NOT SIMPLY CONNECT MULTIPLE EXTENSION CARDS AS A POWER SUPPLY
SLOPPY WORK IN INTERIOR PANEL IMPROPER CONNECTIONS
NEED SMOKE DETECTORS
NEED TO INSTALL GFCI OUTLETS AROUND KITCHEN SINK
HEATER NEEDS TO BE SERVICED
WATER HEATER NEEDS TPRV DISCHARGE LINE
WALLS AND CEILING OF WATER HEATER CLOSET NEED TO BE 1 HOUR FIRE RATED.
EXHAUST VENT FROM WATER HEATER DOES NOT HAVE PROPER CLEARANCES
ELECTRIC WIRING TO COOLER AND BEDROOM HAZARDOUS
04/17/2000 ELECTRIC - FINAL Correction Required ADDTL COMMS - SUPPORT SUB-PANEL FEEDING M.H. GROUND SYSTEM PER N.E.C. MUST HAVE APPROVED CONNECTION AND CORD LISTED FOR MOBILE HOME USE SUB-PANEL MISSING DEAD FRONT COVER. OWN NOT HOME, COULD NOT ACCESS INSIDE COULD NOT LOCATE METER
04/17/2000 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*