Inspection Status: Correction Required
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 04/13/2000 |
ELECTRIC - SERVICE UPGRADE |
|
Correction Required |
ADDTL COMMS - COMPLETE ID BREAKER SCH. BOND NEUTRAL BAR TO GROUND BAR BOND GAS PIPING SYSTEM INSTALL GROUNDING BUSHING ON 1 CONDUIT AT ENTRANCE TO PANEL (CONCENTRIC KO COMING APART) INSTALL GROUNDING CONDUCTOR IN CONDUIT TO AC UNIT LICENSED CONTRACTOR (ELECTRICAL)? |