Inspection Status: Correction Required
Inspection History: ELECTRIC - SERVICE RELOCATION
| Date |
Description |
Inspector |
Results |
Comments |
| 03/29/2000 |
ELECTRIC - SERVICE RELOCATION |
|
Correction Required |
ADDTL COMMS - OK TO CLEAR SERVICE INCREASE CALL FOR FINAL WHEN CHANGE OVER COMPLETE |
| 03/29/2000 |
ELECTRIC - SERVICE RELOCATION |
|
Partial Approval |
OK SER INC CALL FOR 2090 |
| 03/28/2000 |
ELECTRIC - SERVICE RELOCATION |
|
Not ready for Inspection |
NOT READY FOR INSPECTION |
| 03/27/2000 |
ELECTRIC - SERVICE RELOCATION |
|
Correction Required |
ADDTL COMMS - 1. SERVICE TOO HIGH-HIGHEST CIRCUIT BREAKER CAN ONLY BE 67 HIGH. 2. ADDRESS SERVICE 3. GROUND RODS REQUIRED TO BE 6 APART AND FLUSH TO GRADE 4. GROUND WIRE TO BE STRAPED 5. GROUND WIRE GOING THUR 1 1/4 HOLE-NEEDS TO BE SEALED 6. SEAL ROOF JACK 7. RISER IS ABOVE 3 NEEDS GUY BACK 8. BOND GAS AND WATER LINE 9. MAKE GROUND WIRE CONTINOUS TO GROUND RODS 10. IF NOT OWNER OCCUPPIED OBTAIN A C-11 LICENSED ELECTRICAL CONTRACTOR TO DO WORK 11. DO NOT USE SHOT PIN ON WOOD USE AT LEAST 1/4 BOLT. |
| 03/27/2000 |
ELECTRIC - SERVICE RELOCATION |
|
Denied |
DENIED |