Inspection Status: Correction Required
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/24/2000 |
ELECTRIC - FINAL |
|
Correction Required |
ADDTL COMMS - WIRING TO REAR BLDG HAS BEEN REMOVED. DO F.U. INSP FOR 6 MONTHS. FOR MIN HSG, ON REAR UNIT ONLY |
| 03/21/2000 |
ELECTRIC - FINAL |
|
Correction Required |
ADDTL COMMS - 1. INSTALL SMOKE DECTECTOR IN HALL 2. GROUNDING RECEPTACLES NOT TO BE USED ON TWO WIRE CIRCUIT(UNLESS GFCI PROTECTED) 3. OVERHEAD LINES FEEDING BACK BUILDING NEED TO BE REMOVED OR BROUGHT UP TO MEET N.E.C. 4. IF BACK BUILDING TO BE USED THEN INSTALL SEPERATE GROUNDING ELECTRODE SYSTEM AND REMOVE SHEETROCK FOR INSPECTION. 5. INSTALL MISSING DEAD FRONT COVERS AT BOTH ELEC, SERVICE PANELS. 6. INSTALL CORRECT SIZED BREAKER FOR BACK BUILDING 7. PROPERLY SPLICE GROUNDING CONDUCTERS AT J-BOX AT SERVICE 8 J-BOX IS LOOSE (RESECURE) 9. ANCHOR RISER SECURELY TO STRUCTURE 10. A C-11 LIC CONTRACTOR WILL BE REQUIRED TO MAKE CORRECTIONS A 1-HOUR ELEC, REPAIR PERMIT IS REQUIRED. 11. CHANGE OUTLET BY THE SINK TO GFC I TYPE |
| 03/21/2000 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999* |