Permit: T00CM06232


Addresses:

3021 N GAIA PL

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/22/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000* SENT TO TEP ON 10/30/02 AT 2:15PM OK FINAL SUBJECT TO OTHER INSPECTIONS.
07/11/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*1.) BATH FIXTURE TO LISTED AND LABELED. 2.) #8 ROMEX CABLE IS ONLY RATED FOR 40AMPS 336-21. 3.) SUB PANEL CAN NOT BE LOCATED IN A CLOSET WITH COMBUSTABLES 240-24. 4.) LEVEL SURFACE IN FRONT OF A/C DISCONNECT TO BE 36" 5.) FINISH MAKE UP AS SERVICE 6.) CLEAN UNDER LUG.