Permit: T00CM06230


Addresses:

3017 N GAIA PL

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
05/22/2002 MECHANICAL - FINAL Approved IVRS - Inspection 0000*
05/21/2002 MECHANICAL - FINAL Denied IVRS - Inspection 0999*REFEE DUE!! AIR HANDLER INCORRECTLY FUSED. MAX FUSE SIZE FOR AIR HANDLER IS 30AMPS. WHAT SIZE CIRCUIT BREAKER WAS ALLOWED FOR AIR HANDLER IN PANEL?40 AMPS! DOES THIS MEET SPEC'S??NO! WHO'S RESPONSIBILTY IS IT? PLATE HIS JOB! ITS NOT ANYONE ELSE'S RESPONSIBLITY.
05/17/2002 MECHANICAL - FINAL Denied IVRS - Inspection 0999*CONDENSOR NOT INSTALLED YET BE SURE CIRCUIT TO AIR HANDLER IS SIZED PER MANUFACTURERS SPECS.