Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 05/22/2002 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 05/21/2002 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*REFEE DUE!! AIR HANDLER INCORRECTLY FUSED. MAX FUSE SIZE FOR AIR HANDLER IS 30AMPS. WHAT SIZE CIRCUIT BREAKER WAS ALLOWED FOR AIR HANDLER IN PANEL?40 AMPS! DOES THIS MEET SPEC'S??NO! WHO'S RESPONSIBILTY IS IT? PLATE HIS JOB! ITS NOT ANYONE ELSE'S RESPONSIBLITY. |
| 05/17/2002 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*CONDENSOR NOT INSTALLED YET BE SURE CIRCUIT TO AIR HANDLER IS SIZED PER MANUFACTURERS SPECS. |