Permit: T00CM06230


Addresses:

3017 N GAIA PL

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/28/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000* OK FINAL.
05/24/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0245*NOTES LOCKOUT DEVICE FOR W/H BREAKER PROPER DEVICE, MUST HAVE FEATURE FOR LOCKOUT TO KEEP BREAKER OFF DURING MAINT.
05/23/2002 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*AC DISCONNECT NEEDS 36" CLEARANCE IN FRONT. 2.) USE HACR TYPE BKR IF MOVING SW TO PNL. 3.) NEED 1-20A BKR FOR BATH 2 FOR KIT CORRECT SCHEDULE.
05/21/2002 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*
05/19/2002 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*