Inspection Status: Approved
Inspection History: ELECTRIC - TEMPORARY SERVICE
| Date |
Description |
Inspector |
Results |
Comments |
| 02/07/2002 |
ELECTRIC - TEMPORARY SERVICE |
|
Approved |
IVRS - Inspection 0000* |
| 02/05/2002 |
ELECTRIC - TEMPORARY SERVICE |
|
Denied |
IVRS - Inspection 0999*OK CABLE DROP ONLY DO NOT ENEGIZE. 1.) PLEASE SECURE GROUNDING ELECTRODE CONDUCTOR 2.) USE APPROVED FITTINGS TO CONNECT JUNCTION BOX FOR TEMP POWER OUTLET A CHASE NIPPLE IS NOT APPROVED 110-3. 3.) PANEL COVER IS NOT SECURE IT IS FALLING OFF WHEN OPEN 4.) IT APPEARS WE HAVE #14GA WIRE ON A20 AMP BREAKERS PLEASE MATCH AMPACITY 310.5.) PLEASE VERIFY BOND IS POSTED. |