Permit: T00CM06230


Addresses:

3017 N GAIA PL

Inspection Status: Approved

Inspection History: ELECTRIC - TEMPORARY SERVICE

Date Description Inspector Results Comments
02/07/2002 ELECTRIC - TEMPORARY SERVICE Approved IVRS - Inspection 0000*
02/05/2002 ELECTRIC - TEMPORARY SERVICE Denied IVRS - Inspection 0999*OK CABLE DROP ONLY DO NOT ENEGIZE. 1.) PLEASE SECURE GROUNDING ELECTRODE CONDUCTOR 2.) USE APPROVED FITTINGS TO CONNECT JUNCTION BOX FOR TEMP POWER OUTLET A CHASE NIPPLE IS NOT APPROVED 110-3. 3.) PANEL COVER IS NOT SECURE IT IS FALLING OFF WHEN OPEN 4.) IT APPEARS WE HAVE #14GA WIRE ON A20 AMP BREAKERS PLEASE MATCH AMPACITY 310.5.) PLEASE VERIFY BOND IS POSTED.