Permit: T00CM06229


Addresses:

3015 N GAIA PL

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/09/2002 ELECTRIC - FINAL Approved NO WORK PROGRESS PER RICK. OK FINAL.
04/08/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0950*NO WORK PROGRESS.
04/04/2002 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*
04/02/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0935*2.) WHEN A BREAKER IS USE AS A BACKFILL DEVICE IT IS REQUIRED TO HAVE A MANUFACTURES HOLD DOWN DEVICE 384-16. 3.) PLAN REVISIONS TO HAVE APPROVED PLANS EXAMINER STAMP.
03/29/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0999*1. SUBPANEL IN CASITA : A. CANNOT BE IN A CLOTHES CLOSET 240-24(D) B. WE NEED A MAIN BREAKER 225-31 & 32 C. WE NEED TO HAVE LOAD CALC. & REVISED PANEL SCHEDULE. D. THE CURRENT SIZED FEEDER WILL BE NEEDED. E. MAINTAIN WORKING CLEARANCES 110-26 2. SHEET METAL SCREWS CANNOT BE USED FOR GROUNDING AT BATH LITES. 3. WATER HEATER NEEDS TO HAVE A DISCONNECT MEANS & TIGHTEN FITTINGS. 4. TIGHTEN DISCONNECT IN FURNACE AREA & STRAP FLEX. 5. FITTING AT FLOW SWITCH NEED TO BE APPROVED FOR USE.
03/26/2002 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*
03/24/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0999* 1.) WORKING CLEARENCES INFRONT OF SUBPANEL MUST BE MAINTAINED. 2.) PLEASE GROUNDED AND GROUNDING CONDUCTORS AT SUBPANEL AND PANEL. 3.) SEALITITE CONDUIT IS TO BE