Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
| Date |
Description |
Inspector |
Results |
Comments |
| 03/24/2002 |
ELECTRIC - UNDERGROUND |
|
Approved |
IVRS - Inspection 0000*1.) WORKING CLEARENCES IN FRONT OF SUB PANEL MUST BE MAINTAINED 110-26. 2.) PLEASE GROUNDED AND GROUNDING CONDUCTORS AT SUBPANEL AND PANEL. 3.) SEALTITE CONDUIT IS TO BE SECURED AS PER CODES 4.) AN OUTLET PLATE IS MISSING. 5.) PLEASE USE APPROVED FITTINGS WITH SEALTITE AT FLOW SWITCH. 6.) FILL UNUSED OPENINGS AT FIRE BELL. 7.) SWITCHES NEED TO BE GROUNDED 380-9. 8.) PLESE GROUND BATH BAR HOUSINGS. 9.) WORKING CLEARANCES IN FRONT OF A/C DISCONNECT MUST BE MAINTAINED. ALSO PLEASE LABEL 10.) USE APPROVED CONNECTIONS FOR TERMANATION AN MAIN PANEL 11.) BONDING ARE NEEDED AT MAIN PANEL. |
| 03/12/2002 |
ELECTRIC - UNDERGROUND |
|
Not ready for Inspection |
IVRS - Inspection 0000* A REFEE CAN BE ASSESSED IF WORK PROGRESS IS NOT MOVING FORWARD AND INSPECTION ARE CALLED IN WITH NO PROGRESS. |
| 03/11/2002 |
ELECTRIC - UNDERGROUND |
|
Not ready for Inspection |
IVRS - Inspection 0000*1. UNCOVER PVC TO VERIFY CONNECTION AT CASITA 2. INSTALL PVC IN TRENCH 3. PVC UNDERSLAB AT UNIT NOT INSPECTED. |