Permit: T00CM06227


Addresses:

3011 N GAIA PL

Inspection Status: Partial Approval

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
10/25/2001 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*
10/25/2001 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*1.) BOX FOR CLOSET FIX 2.) FLOW SW ROMEX THUR WALL.
10/24/2001 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000*1.) NUMBER REFERNCED ABOVE NOT CORRECTED 2.) RANGE OR PANEL 50A 2P. ON SITE 30A 2P. 3.) ISLAND RECEPTACLE MISSING. 4.) IN CLOSETS INSTALL A BOX FOR FIXTURES 5.) CONNECT FLOW SW IN CLOSET USE PROPER WIRING METHODS 6.) PANEL DOES NO COINCIDE WITH NEW APPROVED PANEL SCHEDULE INSTALL ORDER OF PANEL CIRCUITS AS PER NEW APPROVED PANEL SCHEDULE TO CHECK BREAKER SIZES 7.) PC LIGHT IN AC ROOM MISSING.
10/23/2001 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*
08/29/2001 ELECTRIC - INTERMEDIATE Denied 1.) WIRING PLANS REVISED APASTILLY SINCE PLANS STAMPED BY ELECTRICAL ENGINEER MUST HAVE HIS APPROVAL TO CHANGE-QUITE A FEW CIR'S REMOVED ALSO 20'S TO 14AMPS 2.) REMOVE TIE BAR CONNECTING NEUTRAL & EQUIPMENT GROUNDS AT SUB PANEL CAN ONLY BE TOGETHER AT SERVICE 3.) CONDUCTORS ENTERING SUB PANEL MUST BE INDIVIDUALLY CLAMPED TO ENCLOSURE. 4.) ALL METAL DEVICE BOXES TO BE GROUNDED (SOME MISSING GROUND SCREWS) 5.) SUPPORT PANEL FEEDERS ON 2ND FLOOR. 6.) GROUND ALL OUTSIDE LIGHT BOXES.