Permit: T00CM06225


Addresses:

3007 N GAIA PL

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
05/31/2002 MECHANICAL - FINAL Approved IVRS - Inspection 0000*CORRECTIONS HAVE BEEN MADE.
05/30/2002 MECHANICAL - FINAL Denied IVRS - Inspection 0999*YOU CANNOT HAVE THE ELEC. DISCONNECT FOR THE CONDENSOR UPSTAIRS IN A CLOSET. SHOULD BE WITHIN SIGHT & ADJACENT TO THE EQUIPMENT. RECALL FOR FINAL.
05/29/2002 MECHANICAL - FINAL Denied IVRS - Inspection 0999*PROVIDE A ELEC. DISCONNECT AT CONDENSOR. COULD NOT GET INSIDE DUE TO WET FLOORING RECALL FOR INSPECTION.
05/22/2002 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*
05/17/2002 MECHANICAL - FINAL Denied IVRS - Inspection 0999*60 AMP CIRCUIT TO AIR HANDLER IS TOO LARGE 30 AMP IS MAX SEE MANUFACTURERS DATA PLATE. CONDENSING UNIT NOT INSTALLED YET.