Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 05/31/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 05/30/2002 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*1.) DISCONNECTING MEANS TO BE WITHIN SITE OF OUTSIDE. A/C UNIT. |
| 05/29/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) PLEASE CORRECTLY WIRE A/C DISCONNECT ON CASITA 2.) WE HAVE LOOSE SEAL TITE FITTINGS A/C ON CASITA. 3.) OUTLET RECPETCALES SPACING REQUIRED AS PER CODE 210-52. 4.) AN EXTENDER RING IS NEEDED WHERE DEVICE IS OVER 1/8" PAST BOX 5.) RECEPTICAL TO HAVE ONLY ONE WIRE UNDER GROUND SCREW AND DEVICE SCREWS SHOULD BE SCREWED IN TO PREVENT CONTACT WITH METAL BOXES. 6.) PLEASE CLEAN BUSS OF FORIGEN MATERAL AT SUB PANEL.. |
| 05/24/2002 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 05/22/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*AC UNIT NOT IN, NEED TO COVER ELECT TRENCH, LIGHT UNDER KIT CABINET MISSING HAVE ELECTRICIAN CHECK UNIT OUT FOR FINAL PRIOR TO CALLING HAVE ALL ITEMS WORKING FOR TESTING. |
| 05/17/2002 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000* |