Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 01/17/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*FINAL APPROVED ELECTRICAL C OF O SUBJECT TO OTHER INSPECTORS ENGINEERS LETTER APPROVED IN OFFICE IN LIEU OF TEST LAB LISTING. |
| 12/13/2001 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*NOT READY RECEIVED INFORMATION AND LETTERS IN LIEU OF LISTING WILL CONSUIT WITH RAY. |
| 11/19/2001 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*NEED CITY APPROVED STAMP FOR LISTING ON SPRAY BOOTH, BY ENGINEED 2.) EXHAUST FAN NEEDS PROPER LISTING BY OSHA APPROVED TEST LAB CL.I. DIV. I. |
| 11/15/2001 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*1.) NEED LETTER FROM ELECTRICAL ENGINEER (IN LIEU OF LISTING ON ACCEPTANCE OF COMPLETE SPRAY BOOTH (XCEPT EXHAUST FAN) NEED ACT NO ENGINEER STAMP, ADDRESS 2.)NO LISTING FOUND ON EXHAUST SYSTEM MUST HAVE A LISTED UNIT. 3 A.D.T. ALARM SWITCHING NOT LISTED FOR CC I, DIV II. 4) 2 END FIXTUREER IN 3FT RADIUS OF CC.I. DIV II. |
| 11/07/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0333*NO PERSONAL FROM CONTRACTOR HERE WITH REVISION PLEASE RECALL. |
| 10/30/2001 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 10/03/2001 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*1.) GROUND TRANSFORMER (CRANE) 2.) NEED APPROVED CITY REVISIONS NOTES ETC. PLAN FOR NEW TRANSFORMER AND CRANE, DERATE PAPER. 3.) NEED U.C. OR EQUIVALENT LISTING FOR SPRAY BOOTH 4.) NEED 30 KAIC RATED FOR PANEL A OR CITY APPROVED REVISED 4.) NEED 30 KAIC RATED FOR PANEL A OR CITY APPROVED REVISED CALC. (65FT TOTAL LENGTH) 5.) NEED SEAL OFF AT MICRO SWITCHES 6.) REROUTE TOGGLE SWITCHES AND CONDUIT OR PROVIDE EXPLOSION PROOF SWITCHES AND EQUP. 7.) LOW VOLT DEVICES TO BE APPROVED |
| 09/12/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*DENIED A RE-FEE IN DUE BEFORE THE NEXT INSPECT. 1.) SECONDARY CONDUIT MUST BE UNCOVERED 2.) GROUND ROD CONNECTION MUST BE EXPOSED FOR INSPECTION. 3.) PROVIDE LADDER - NEED ACCESS TO STEEL BOND. 4.) CANNOT LOCATE WATER BOND CONNECTOR. 5.) NO APPROVED PLANS LOCATED FOR CHANCE (ADDED TRANSFORMENT) WILL NEED GROUNDING FOR SEPERATELY DERIVED SYSTEM? LONLY SEE ONE GROUND ROD, NO BUILD. STEEL. GROUNDING ELECTRODE CONDUCTOR TO BE EXTERNAL AND SEPARATE FROM FEEDER CONDUCTON 6.) TRANSFORMER REVERSED AS FOR AS NAMEPLATE ( NOT LISTED FOR THIS.) 7.) SPRAY BOOTH REQUIRES LISTING AND NAME OF L-11 ELETRICAL 8.) NO LETTER ON CONDUIT DERATE. 9.) CHECK FAULT CURRENT RATE AT PVC A 22 KAIC 11.) A SEAL IRREQUIRED UPON LEAVING THE CLASSIFIED AREA. 12.) TOGGLE SWITCHES IN CLASSIFIED AREA. |
| 09/06/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999* |