Inspection Status: Approved
Inspection History: ELECTRIC - UFER
| Date |
Description |
Inspector |
Results |
Comments |
| 01/17/2002 |
ELECTRIC - UFER |
|
Approved |
|
| 09/06/2001 |
ELECTRIC - UFER |
|
Denied |
IVRS - Inspection 0999*OTHER ITEMS CHECK ALL 1.) SECONDARY CONDUITS COVERED SEE MARTIN TESTER. 2.) GROUND SYSTEM RODS COVERED. GROUND SERVICE PER PLAN OR REVISE PLAN. 3.) NEED TO GROUND BUILD STEEL WATER GAS 4.) GROUND FOR A SEPERATELY DEVICED SYSTEMS 5.0 TRANSFORMER BEING REVERSED FED. (MUST BE 208 TO 480/ 6.) NEED PROPER PER PLANS, FOR SPRAY BOOTH NEED LICENSED CONTRACTOR AND ENGINEER FOR BOOTH.7.) DERATE CONDUCTOR FEED FOR PANEL A. |