Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/17/2001 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection 0000* | |
| 08/31/2001 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection 0999*/ 1) BUILD UP STUDS AT HEADERS, CORNERS AND POST ARE NOT BUILT OR FASTENED PER IRC, BUILD TO CODE OR PROVIDE CITY APPROVED ENGINEERINGS FOR SCREWS/BUILD UP OR HAVE AND BUILD TO LIGHT WEIGHT STEEL FRAME CONSTRUCTION STANDARDS 2) PROVIDE CITY OF TUCSON APPROVAL OF PLAN REVISION 3) PROVIDE ACCESS TO JACCUZI HEAD OFF ACCESS 4) PROVIDE PROPER CHAFE PROTECTION FOR PEX 5) SCREW PROTECT PLUMBING WITHIN 1 1/4" OF STUD SURFACE | |
| 08/21/2001 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection 0999*/ 1) L HEADERS NOT SCREWED TO TOP TRACK PER 18/47 12" ON CENTER 2) PROVIDE TRUSS DESIGN FOR GARAGE HEADER-GIRDER TRUSS 3) TRUSS DRAWINGS MUST BE APPROVED BY CITY OF TUCSON 4) NORTHEAST SHEARWALL 1 MUST BE 7'-11" NOW 5'-0" 5) SOUTHWEST SHEARWALL MUST BE 12'-0" NOW 6'-0" 6) TRACK HILT-PINS REQUIRED AT 12" ON CENTER SEE 14/6 7) PORCH POST TO BEAM CONNECTION NOT MADE SEE 2/5 8) PROVIDE DETAIL OF 6 X 12 BEAM CONNECTION TO STEEL STUD WALL 9) OK-TO DRY IN ROOF ONLY |
|
| 08/15/2001 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection 0999*/ 1) NEED ENGINEERED STEEL PACKET ON SITE UNABLE TO DETERMINE REQUIRED SCREW PATTERN AT L HEADERS 2) COMPLY W/DETAIL 7 SHEET 6 FOR TOP 3) ENGINEERED SCREW SCH FOR ROOF SHEATHIN REQUIRED |