Permit: T00CM06212

Parcel: 133031190


Addresses:

9501 E CALLE EUNICE

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
03/15/2001 FRAMING Approved IVRS - Inspection 0000*
03/13/2001 FRAMING Not ready for Inspection IVRS - Inspection 0000*
03/07/2001 FRAMING Denied IVRS - Inspection 0999*/1. INSTALL H2.5'S BOTTOM PLATE TO STUD, STUD TO TOP PLATE ALL EXTERIOR WALLS AND ALL BEARING WALLS. 2. INSTALL 4" NAILING EXTERIOR SHEARWALLS. 3. INSTALL MINIMUM 2 PLATE BOLTS PER 4' SECTION SHEARWALL. 4. SPLITS IN PLATES TO OCCURR OVER STUDS. 5. STRAP FRAME WALL TOP PLATES TO EXISTING BEAM. 6. INSTALL BOLTS IN MASONRY WALL AT NEW FRME WALL. 7. RAMSET INTERIOR BOTTOM PLATES MAX. 32" SPACING. 8. INSTALL H2.5'S INTERIOR BEARING WALLS ALL STUDS TO TOP AND BOTTOM PLATES. 9. INSTALL DOUBLE 2 X 8 HEADER EACH OPENING PER PLAN. 10. INSTALL SOLID 2 X 10 BLOCKING BETWEEN RAFTERS AT BEARING POINTS. 11. INSTALL TRIPLE 2 X 10 BEAM AT BEARING. 12. STRAP BEAM TO BEARING BELOW; BOLT BEAM TOGETHER ADJOINING EXISTING BEAM. 13. INSTALL SKYLIGHT OPENINGS. 14. INSTALL ALL PLYWOOD ROOF SHEATHING.