Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
Permit Number - T00CM06173
Inspection Description - EXT METAL CLIPS/EXT SHEATHING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/26/2001 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection 0000* | |
02/22/2001 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection 0999*/1. SECURE ALL DOUBLE TOP PLATES NOT CABIN TIED. 2. #3 SHEARWALL SECOND FLOOR NOT INSTALLED AS PER PLAN. 3. HOLDOWNS NEED TO BE INSTALLED TO FULL HEIGHT DBL STUDS. 4. DETAIL 3/SD3 NOT INSTALLED AT GARAGE FRONT STRAP AND TRIPPLE KINGS. 5. JACK TRUSSES FRONT GARAGE NAILED THRU BACK SEE DETAIL 7/SD2 FOR CORRECT APPLICATION. 6. DETAIL 6/SD1 NOT COMPLETE AT FRONT COLUMNS. 7. PROVIDE 1/8 INCH GAP AT OSB PANEL ENDS AND EDGES. |