Permit: T00CM06173

Parcel: 141113170

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Permit Number - T00CM06173

Inspection Description - EXT METAL CLIPS/EXT SHEATHING

Inspection Status - Approved

Date Description Inspector Results Comments
02/26/2001 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection 0000*
02/22/2001 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection 0999*/1. SECURE ALL DOUBLE TOP PLATES NOT CABIN TIED. 2. #3 SHEARWALL SECOND FLOOR NOT INSTALLED AS PER PLAN. 3. HOLDOWNS NEED TO BE INSTALLED TO FULL HEIGHT DBL STUDS. 4. DETAIL 3/SD3 NOT INSTALLED AT GARAGE FRONT STRAP AND TRIPPLE KINGS. 5. JACK TRUSSES FRONT GARAGE NAILED THRU BACK SEE DETAIL 7/SD2 FOR CORRECT APPLICATION. 6. DETAIL 6/SD1 NOT COMPLETE AT FRONT COLUMNS. 7. PROVIDE 1/8 INCH GAP AT OSB PANEL ENDS AND EDGES.