Permit: T00CM06158

Parcel: 140420740


Addresses:

7250 S TUCSON BL

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
06/20/2001 PLUMBING - FINAL Approved IVRS - Inspection 0000*1)WATTS 007 #26486-FOR WATER SUPPLIED KITCHEN APPLIANCES.2)OK FOR
C OF O PENDING VERTIFICATIONOF CERTICATION OF BACKFLOW PREVENTERS.
06/19/2001 PLUMBING - FINAL Denied IVRS - Inspection 0999*1)ALL CORRECTION MADE OK EXCEPT COFFEE MAKERS.2)AFTER READING INSTALLATION MANUAL AND EXAMING COFFEE BREWER, I OBSURRED THE SUBMERGED INLET TO THE RESERVOIR.THERE IS NO AIR GAP, ONLY AN AIR BREAK.PORTABLE WATER NEEDS PROTECTION.
06/18/2001 PLUMBING - FINAL Denied IVRS - Inspection 0999*1)NO CHARGE FROM LAST INSPECTION.2)SEE NOTES FROM 06 06 01 AND COMPLY.3)ALL KITCHEN EQUIPMENT USING POTABLE WATER AND HAVING A SUBMERGED INLET REQUIRE BACKFLOW PROTECTION.4)ALL SODA FOUNTAIN DISPENSERS USING A CARBONATOR REQUIRE RPBP.5)CONTRACTOR TO PAY RE-INSPECTION FEE.
06/17/2001 PLUMBING - FINAL Denied IVRS - Inspection 0999*
06/15/2001 PLUMBING - FINAL Denied 1. ALL WATER SUPPLIED FOUNTAIN DISPENSORS, COFFEE MAKERS, ICED TEA MAKERS ETC SHALL HAVE PRIMARY BACKFLOW PROTECTION DEVICES INSTALLED.
2.) KITCHEN EQUIPMENT DRAINS (INDIRECT) SHALL HAVE A MINIMUM 1" AIR GAP
3.) INDIRECT WASTER PIPING AND PRBP DRAINS SHALL BE SUPPORTED AND BRACED
06/06/2001 PLUMBING - FINAL Denied IVRS - Inspection 0999*1)PLEASE REVIEW REQUIREMENTS FOR INDIRECT WASTE PIPING INCLUDING AIR GAP REQUIREMENTS.2)ALL OVERHEAD PIPING CONCEALED.3)WATER GROPS FOR MAKER DO NOT INCLUDE BACK FLOW PROTECTION.