Permit: T00CM06143

Parcel: 128040850

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
04/10/2001 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*/1. NEED ONE GROUND ROD. 2. INSTALL GRD. BUSS, FOR GRD WIRES, LEAVE NEUTRALS ON ISOLATED NEUTRAL BUSS. 3. WHITE TAPE, RED TAPE, ENDS OF CONDUCTORS.
04/05/2001 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000*/1. # AT FINAL ALL ROMEX TO BE PROTECTED TO 8' HT OR CIELING HT. 2. YOU NEED A GROUNDING SYSTEM ELECTOR #4 TO A GROUND ROD OR RUN A GRD. WIRE IN YOUR CONDUIT TO THE SERV. 3. PLAN SHOWS 110 CAPABILITY ONLY FOR SUB-PANEL BUT YOU STILL NEED TWO INSULATED WIRES AND GROUND SYSTEM. 4. PLASTIC CONDUIT, WAS IT INSPECTED? 18" OF DEPTH/COVER.