Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 04/10/2001 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000*/1. NEED ONE GROUND ROD. 2. INSTALL GRD. BUSS, FOR GRD WIRES, LEAVE NEUTRALS ON ISOLATED NEUTRAL BUSS. 3. WHITE TAPE, RED TAPE, ENDS OF CONDUCTORS. |
| 04/05/2001 |
ELECTRIC - INTERMEDIATE |
|
Not ready for Inspection |
IVRS - Inspection 0000*/1. # AT FINAL ALL ROMEX TO BE PROTECTED TO 8' HT OR CIELING HT. 2. YOU NEED A GROUNDING SYSTEM ELECTOR #4 TO A GROUND ROD OR RUN A GRD. WIRE IN YOUR CONDUIT TO THE SERV. 3. PLAN SHOWS 110 CAPABILITY ONLY FOR SUB-PANEL BUT YOU STILL NEED TWO INSULATED WIRES AND GROUND SYSTEM. 4. PLASTIC CONDUIT, WAS IT INSPECTED? 18" OF DEPTH/COVER. |