Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T00CM06126
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/29/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
11/28/2001 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*MECH ROOM 1.) INSTALL HEATERS IN STARTERS 2.) NEED BOND BUSHING AT 1-DISCONNECT. 3.) LABEL ALL STARTERS & DISCONNECTS. | |
11/21/2001 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* DOUBLE LUGGING IN MECHANCLE ROOM DISCONNECTS AND WATER HEATER DISCONNECT. 2) LOOSE SEAL TIGHT FITTINGS AND FLEX FITTING. 3) EXPOSED CONDUCTORS. 4) STRAP FLEX AS PER CODE. 5) NEED DISCONNECTING MEANS FOR INSTA HOT. 6) FINISH MECHANICAL YARD. | |
10/25/2001 | ELECTRIC - FINAL | Denied | DENIED A REFEE IS DUE BEFORE THE NEXT INSPECTOR USING A RED WING NUT (WIRE NUT) TO SPLICE (2) #6 AWG WIRER, COPPER AND ALUMINUM. |