Permit: T00CM06126

Parcel: 116193570


Addresses:

420 N BONITA AV


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T00CM06126

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/29/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
11/28/2001 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*MECH ROOM 1.) INSTALL HEATERS IN STARTERS 2.) NEED BOND BUSHING AT 1-DISCONNECT. 3.) LABEL ALL STARTERS & DISCONNECTS.
11/21/2001 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000* DOUBLE LUGGING IN MECHANCLE ROOM DISCONNECTS AND WATER HEATER DISCONNECT. 2) LOOSE SEAL TIGHT FITTINGS AND FLEX FITTING. 3) EXPOSED CONDUCTORS. 4) STRAP FLEX AS PER CODE. 5) NEED DISCONNECTING MEANS FOR INSTA HOT. 6) FINISH MECHANICAL YARD.
10/25/2001 ELECTRIC - FINAL Denied DENIED A REFEE IS DUE BEFORE THE NEXT INSPECTOR USING A RED WING NUT (WIRE NUT) TO SPLICE (2) #6 AWG WIRER, COPPER AND ALUMINUM.