Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 03/02/2001 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 02/28/2001 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/1. NO WATER TEST 2. ROMEX WIRE IN BEDROOM DAMAGED AS PER PREVIOUS INSPECTION. 3. ALTERNATIVE HOLDOWN NOT INSTALLED AS PER PREVIOUS INSPECTION BACK SHEARWALL SEE PLAN. 4. BLOCK SHEARWALL AT GARAGE AT CLEAN OUT BORED OVER 4". 5. GIRDER TRUSS NOT CLIPPED BOTH SIDES SEE 2/SD2 DETAIL. 6. TAPE WEATHER BARRIER AT ELEC. PANEL AND STUDY ROOM. |
| 02/26/2001 |
FRAMING |
|
Partial Approval |
IVRS - Inspection 0000*/NO PLANS OR PERMIT CARD ON SITE. ROMEX NOT REPAIRED FROM PREVIOUS INSPECTION RECALL WHEN READY. |
| 02/23/2001 |
FRAMING |
|
Denied |
1. CHECK ANCHOR BOLTS THRU OUT 2. EXPOSE WIRE AT ROMEX WEST WALL OF FRONT BEDROOM. |