Inspection Status: Approved
Inspection History: ELECTRIC - UFER
| Date |
Description |
Inspector |
Results |
Comments |
| 03/26/2001 |
ELECTRIC - UFER |
|
Approved |
IVRS - Inspection 0000* |
| 03/20/2001 |
ELECTRIC - UFER |
|
Denied |
NOTE: UFER GROUND NOT PROPERLY INSTALLED. IT MUST BE CONNECTED WITH BRONZ CLAMP AND BRASE SCREW OR HAVE 20 FEET OF CONTINUOUS COPPER INSTALLED IN TRENCH OR YOU MAY INSTALL 2 EACH 8 FOOT GROUND RODS 6 FEET APART AND CONNECTED TO ELECTRIC SERVICE AFTER SLAB IS POURED OR YOU MAY CALL FOR A 02005 UFER INSPECTION PRIOR TO POURING. |