Permit: T00CM06115

Parcel: 120076720


Addresses:

507 W PRESIDENT ST

Inspection Status: Approved

Inspection History: ELECTRIC - UFER

Date Description Inspector Results Comments
03/26/2001 ELECTRIC - UFER Approved IVRS - Inspection 0000*
03/20/2001 ELECTRIC - UFER Denied NOTE: UFER GROUND NOT PROPERLY INSTALLED. IT MUST BE CONNECTED WITH BRONZ CLAMP AND BRASE SCREW OR HAVE 20 FEET OF CONTINUOUS COPPER INSTALLED IN TRENCH OR YOU MAY INSTALL 2 EACH 8 FOOT GROUND RODS 6 FEET APART AND CONNECTED TO ELECTRIC SERVICE AFTER SLAB IS POURED OR YOU MAY CALL FOR A 02005 UFER INSPECTION PRIOR TO POURING.