Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T00CM06113

Parcel: 131091850


Addresses:

5636 E 26TH ST #02

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
01/29/2002 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*SEE NOTE BELOW ADD A 2ND STUD TO SUPPORT SUB PANELS THANKS.
01/23/2002 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*1.) BOX CLAMPS IN MULTIGANG BOXES TO BE TIGHTEN DOWN.2.) PROTECT NM CABLE IN METAL STUD CHANNEL 300-4. 3.) RANGE CABLE IS TO BE SECURED TO THE BOX 373-5. 4.) A BOX IS NEEDED AT FRONT PORCH LIGHT. 5.) LOW VOLTAGE AND MEDIUM VOLTAGE CAN NOT OCCUPY THE SAME BOX UNLESS THE CONDUCTORS ARE RATED THE SAME 6.) A CONNECTOR IS NEED AT THE EXHAUST FANS. 7.) CONECTORS ARE NEEDED AT CABLE ENTERING THE SUBPANEL ALSO SUPPORT THE CABLES ABOVE THE PANEL AND SUPPORT THE PANEL FROM MOVEMENT. 8.) GAS BOND WIL BE REQUIRED. 9.) SEAL FIRE WALL PENATRATION WITH APPROVED METHODS. 10.) PLEASE PROVIDE SWITCH GROUND ROUGH IN INSPECTION 11.) AN APPROVED PLAN IS TO BE ON JOB SITE.