Inspection History Details
Permit: T00CM06093
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/19/2002 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection 0000*SERVICE NO. 1 AND NO. 2 WILL NEED TO HAVE A COMMON GROUNDING ELECTRODE SYSTEM BETWEEN SERVICE. 250-58. |