Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T00CM06085
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/21/2002 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection 0000* 1.) VENTING FOR LAUNDRY IN A SERIES OK OK TO COVER ALL AREAS. | |
04/30/2002 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*1.) BLDG ONE AND RECREATION BLDG. ABS DWV OK WATER TEST OK. 2.) CPVC WATER PIPE OK PRESSURE TEST OK 3.) TUBS AND CLOSET FLANGES OK 4.) ROOF DRAINS OK 5.) OK TO COVER EVERYTHING BUT VTR FOR LAUNDRY TUB. | |
04/25/2002 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0999*1.) CPVC TO BE SUPPORTED 3' MAX. 2.) ROOF DRAIN AND OVERFLOW COMBINED AT FOUR INCH. INCREASE T0 6" AT SECOND 4" TEE. 3.) YARDWATER CONNECTIONS OK OK TO COVER. | |
04/05/2002 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000*1.) YARDWATER NOT INSTALLED PER PLAN. PLAN REQUIRES TYPE "L" COPPER OR SCH 40 PVC. | |
01/28/2002 | PLUMBING - INTERMEDIATE | Cancelled | IVRS - Ri canceled |