Permit: T00CM06038

Parcel: 141112800

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T00CM06038

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
02/26/2001 FRAMING Approved IVRS - Inspection 0000*
02/22/2001 FRAMING Denied IVRS - Inspection 0999*/1. ISOLATE ROMEX CABLE NO BUNDLING AT ATTIC. 2. SECURE PEX LINES PER MANUF. SPECS OR 4' O.C. 3. DETAIL 15/SD3 NOT COMPLETE DETAIL 3/SD3 TRIPLE TRIMMERS AT 2 X 4 WALLS. 4. DETAIL 6/SD2 NOT COMPLETE. 5. PROVIDE 10 PSI FOR GAS LINE TEST. 6. SECURE 90 DEGREE VTR AT BOTTOM WITH APPROVED STRAPS P. TAPE NOT ACCEPTABLE.