Permit: T00CM06031

Parcel: 125043300


Addresses:

2432 E HAWTHORNE ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/20/2000 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
12/19/2000 ELECTRIC - FINAL Denied IVRS - Inspection 0999*/1. A/C CONDUCTORS CANNOT BE RAN THRU AN UNPROTECTED DRILLED HOLE IN SERVICE PANEL. PROVIDE PROTECTION. 2. #6 GROUND FOR A/C CANNOT BE DOUBLE LUGGED WITH HOUSE GROUND INSTALL ON GROUND BAR OR PROVIDE AN APPROVED GROUND LUG KIT. 3. UNABLE TO LOCATE INSPECTION CARD. PLEASE LEAVE IT BY SERVICE PANEL. (ELECT)