Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 11/27/2001 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 11/20/2001 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) YOU CANNOT REDUCE THE SIZE OF THE CONDENSATE DRAIN LINES. MUST BE SAME SIZE AS OUTLET ON UNIT THE ENTIRE LENGTH. 2.) MARK UNIT DATA PLATES W/PROPER HEAT KIT INSTALLED AND FUSE UNTIS ACCORDINALY.3.) PROVIDE ECONOMIZERS AS PER PLANS. RECALL FOR FINAL INSPECTION. |
| 11/19/2001 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*NO CONTRACTOR ON SITE. NO APPROVED PLANS ON SITE. NO ACCESS TO ROOF TOP UNITS. |
| 11/14/2001 |
MECHANICAL - FINAL |
|
Partial Approval |
WANT ROOF TOP ACCESSABLE UNIT FUSING CONDENSATE DATA PLATE ON HEAT PUMP COMPLETED ECT. |