Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 01/15/2002 |
PLUMBING - FINAL |
|
Approved |
1.) ALL CORRECTION MADE OK 2.) PLUMBING FINAL OK 3.) OK FOR C OF O. PENDING ANY OTHER INSPECTION. |
| 01/14/2002 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) HANDICAPPED WATER CLOSETS REQUIRE 18" FROM CENTERLINE TO SIDE WALL OR OBSTRUCTION (INCLUDES TAMPON/TAMPAX DISPOSER). 2.) 3" CLEAN OUTS REQUIRE 18" CLEARANCE IN FRONT OF C.O. 3.) SPIN HOSE DAMP ON CONDENSATE DRAIN SO THERE ARE NO EDGES TO CATCH ON CLOTHING OR SKIN. |