Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T00CM06004
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/15/2002 | PLUMBING - FINAL | Approved | 1.) ALL CORRECTION MADE OK 2.) PLUMBING FINAL OK 3.) OK FOR C OF O. PENDING ANY OTHER INSPECTION. | |
01/14/2002 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999*1.) HANDICAPPED WATER CLOSETS REQUIRE 18" FROM CENTERLINE TO SIDE WALL OR OBSTRUCTION (INCLUDES TAMPON/TAMPAX DISPOSER). 2.) 3" CLEAN OUTS REQUIRE 18" CLEARANCE IN FRONT OF C.O. 3.) SPIN HOSE DAMP ON CONDENSATE DRAIN SO THERE ARE NO EDGES TO CATCH ON CLOTHING OR SKIN. |