Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 10/08/2001 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 09/07/2001 |
FRAMING |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) PROVIDE A CITY OF TUCSON APPROVED DETAIL FOR HEADERS ON METAL FRAMED BEARING WALLS 2) PROVIDE CITY OF TUCSON APPROVAL FOR ALL PLAN REVISING 3) W/C FLOOR FLANGE NOT INSTALLED 4) NO GAS PRESSURE TEST |
| 08/21/2001 |
FRAMING |
|
Denied |
IVRS - Inspection 0950$/ 1) BLOCK DEFUSER BOOTS 3 SIDES 2) FURRED WALL AT KITCHEN VENT NOT SECURE 3) POST TENSION SLAB CUT TO RELOCATE WATER CLOSET PROVIDE ENGINEERS APPROVED EVALUATION/REPAIR 4) REVISE PLAN FOR SHOWER AND HANDICAP BATH 5) PLAN CALLS FOR GALVANIZED DUCT, FLEX INSTALLED, BUILD TO PLAN OR REVISE TO ASBUILT 6) BEARING WALLS REQUIRE HILTI PINS AT 16" ON CENTER 7) STUDS MISSING IN BEARING WALL 8) PROTECT WIRES WITHIN 1-1/4" OF STUD SURFACE 9) REMOVE ALL INSULATION |
| 08/20/2001 |
FRAMING |
|
Denied |
IVRS - Inspection 0950* |