Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/21/2000 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000* | |
| 12/20/2000 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0245* ROMEX NOT APPROVED IN EXAM ROOM MUST COMPLY WITH ART 517 NEC |