Inspection History Details
Permit: T00CM05963
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/17/2001 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000* ALL WALL ROUGH IN OK |
|
| 01/12/2001 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0245* SUITE #100 NOTES: EMT MUST BE SUPPORTED WITHIN 3' EACH BOX ALSO NOTE CONDUIT MUST BE SUPPORTED AGAINST METAL STUDS, NO GAPS BETWEEN STUDS AND CONDUIT |