Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/19/2001 |
BUILDING - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 03/14/2001 |
BUILDING - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/MISSING CERTIFICATES. |
| 03/12/2001 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0925*/1. IDENTIFY SMOKE DETECTORS AT PANEL AS PER MANF. SPEC. 2. GAS LINE BOND WIRE NOT SECURED WITH CLAMP. 3. PROPERTY ADDRESS NOT POSTED. 4. SEE NEC. 210.52 RECEPS NOT PERMITTED COUNTER OVER HANGS EXCEEDINGS 6". |