Permit: T00CM05914

Parcel: 13505149G

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/02/2001 ELECTRIC - FINAL Approved APPROVED OK TO CLEAR
06/29/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0920*
06/27/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999*1.) ON RISER ENTRY INTO METER SECTION USE LN ON BOTTOM & INVERT INSIDE ONE TO BITE CAN 2.) RUN JUMPER FROM NEUTRAL TO GROUND LUG. 3.) TRANS SW LABELS GEN FEED & REG POWER. 4.) PLAN CALLS FOR SUPPRESSOR TUSS TO BE WIRED WITH 3 #8 AND 1 #8 GROUND IN 3/4" CONDUIT YOU HAVE 1/2" CONDUIT WITH 3 #8S. 5.) LABELS 200A SW GEN POWER
06/13/2001 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*