Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date |
Description |
Inspector |
Results |
Comments |
| 12/20/2000 |
PLUMBING - ROUGH, SOIL |
|
Approved |
IVRS - Inspection 0000* |
| 12/19/2000 |
PLUMBING - ROUGH, SOIL |
|
Denied |
IVRS - Inspection 0999*/1. CHICAGO LOOP NOT APPROVED 2. STAKE HORIZONTAL BRANCHES OR PROVIDE SHADING. 3. A RE INSPECTION FEE WILL BE IMPOSED IF CALLED IN AGAIN WITHOUT CHANGES. 4. PROVIDE SAN TS AND CLEANOUTS AT ROUGH SOIL OR RE TEST ALL STACKS AT INTERMEDIATE DRAINS. |
| 12/18/2000 |
PLUMBING - ROUGH, SOIL |
|
Denied |
IVRS - Inspection 0999*/1. CHICAGO LOOP NOT INSTALLED CORRECTLY. SEE UPC SPECIAL VENT SYSTEMS OR PROVIDE AN AIR ADDMITTANCE APPLICATION. 2. POSITIVELY SUPPORT HORIZONTAL BRANCH LINES AT TUB/SHOWER AND SEWER CONNECTION. 3. OK TO BACK FILL PLUMBING YARD WATER NO TEST. |