Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 02/22/2001 |
ELECTRIC - ABOVE CEILING |
|
Approved |
IVRS - Inspection 0000* |
| 02/16/2001 |
ELECTRIC - ABOVE CEILING |
|
Denied |
IVRS - Inspection 0999* 1) CONDUIT AND BOXES ABOVE CEILING GRID MUST BE SUPPORTED BY SUPPORT WIRES INDEPENDANT OF CEILING WIRES AND THE WIRES MUST BE TIED BOTH TOP AND BOTTOM SO AS TO BE TAUGHT TO PREVENT SWING ACTION. SEE NEC 300-11, 300-11(A), AND 370-23(D) 1&2. 2) DROP-IN FIXTURES MUST BE EITHER SCREWED TO GRID OR HAVE ALL FOUR CLIPS TURNED OUT |