Permit: T00CM05840

Parcel: 13348128A

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
02/22/2001 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection 0000*
02/16/2001 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0999* 1) CONDUIT AND BOXES ABOVE CEILING GRID MUST BE SUPPORTED BY SUPPORT WIRES INDEPENDANT OF CEILING WIRES AND THE WIRES MUST BE TIED BOTH TOP AND BOTTOM SO AS TO BE TAUGHT TO PREVENT SWING ACTION. SEE NEC 300-11, 300-11(A), AND 370-23(D) 1&2. 2) DROP-IN FIXTURES MUST BE EITHER SCREWED TO GRID OR HAVE ALL FOUR CLIPS TURNED OUT