Permit: T00CM05830

Parcel: 141112850


Addresses:

8433 E HODGMAN PL


Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T00CM05830

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
04/10/2001 FRAMING Approved IVRS - Inspection 0000*
03/13/2001 FRAMING Partial Approval IVRS - Inspection 0000*/TRUSS ENGINEERING MUST BE APPROVED BY C.O.T. OK TO INSULATE AND DRYWALL.
03/12/2001 FRAMING Denied IVRS - Inspection 0999*/FINISH BLOCKING REGISTER AND EXTEND MECH PLATFORM.
02/26/2001 FRAMING Denied IVRS - Inspection 0999*
02/22/2001 FRAMING Denied IVRS - Inspection 0999*/1. DETAIL 15/SD3 NOT COMPLETE. 2. NO TEST ON WATER LINES. 3. DETAIL 6/SD2 NOT COMPLETE. 4. ANCHOR BOLTS NOT COMPLETE AT SOLE PLATES. 5. CLIP GIRDER AS PER PLAN. 6. PROVIDE ENGINEERS FIX AT OVER KNOTCHED SHEARWALL DRYER VENT. 7. SECURE PEX 4' O.C. 8. STAIRWALL LEDGER NOT INSTALLED PER PLAN.