Permit: T00CM05817

Parcel: 136382000


Addresses:

7272 E OLIVE PL

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
02/15/2001 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection 0000*
02/09/2001 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection 0000*/INTERIOR NEW ADDITION PRESS TEST NOT YARD LINE.
02/07/2001 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection 0000*/1. LINE NOT HOLDING PRESS 2. WHITE PLASTIC PIPE YARD LINE LOOKS LIKE PVC USED FOR GAS LINE. 3. COMPRESSION FITTING NEED A LISTING FOR ADAPTING TO WHITE PLASTIC PIPE. 4. IF WHITE PIPE IS APPROVED FOR GAS REPLACE YARD LINE WITH 1" COATED PIPE.