Permit: T00CM05811

Parcel: 137053640


Addresses:

803 W MONTANA ST

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
11/07/2001 FRAMING Approved IVRS - Inspection 0000*
10/30/2001 FRAMING Partial Approval 1) OK TO SHEET ROCK, EXCEPT AT ATTIC UNIT PENDING APPROVAL FROM TRUSS MANUFACTURE OF UNIT LOAD ON BOTTOM CORD AND TRUSSES BEING 1/3 POINT BEARING
10/26/2001 FRAMING Denied IVRS - Inspection 0999*/ 1) OVER BORED STUDS AT REAR 2) DUCT FLEX REQUIRES FRAMED ? 3) A/B'S THRU-OUT 4) BLOCK MISSING AT GABLE TO TRUSS 5) PROVIDE TRUSS CALC'S 6) PROVIDE REVISION FOR H.P. 7) REQUIRES WATER HEATER FLUE 8) SECURE COMBUSTIBLE RELIEF VENTS 9) REQUIRES 2" WASTE AT LAUNDRY DO NOT BACKFILL CONNECTION AT SEWER
10/24/2001 FRAMING Denied IVRS - Inspection 0999*/ 1) PLATFORM FOR ATTIC H.P. NOT IN PLACE 2) H2.5 MISSING AT ALTERNATE STUDS AT INT. BEARING WALL 3) STRAP DOUBLE PLATES TO BEAM AT EXTERIOR WINDOW 4) INPROPER VENT AT TUB
10/19/2001 FRAMING Denied IVRS - Inspection 0999*/ 1) MULTIPLE ITEMS NOT COMPLETE RENEW EXPIRED PERMITS BELOW T97PL00744 AND T97EL00207, GAS LINE EXTENSION EXPIRED
10/17/2001 FRAMING Denied 1) SAME AS BEFORE LAST INSPECTION
10/12/2001 FRAMING Denied 1) BLOCK AIR GRILLS 3 SIDES 2) COMBUSTIBLE AND RELIEF FOR WATER HEATER MISSING 3) PLUMBING NOT COMPLETE 4) HEADERS NOT PER PLAN 5) 1/2" BOLTS REQUIRED 12" MAXIMUM FROM BOTTOM PLATES EDGE 6) REVISE PLAN TO REFLECT ATTIC FURNACE, NEED DEVELOPMENT SERVICES DEPARTMENT APPROVAL 7) HEAT PUMP SHALL NOT BE IN FRONT OF ELECTRIC DISCONNECT 30" WORK SPACE REQUIRED