Permit: T00CM05794

Parcel: 10819008F


Addresses:

4566 N 1ST AV


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T00CM05794

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
12/06/2001 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
11/28/2001 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0935*1.) BOND JUMPER TO BE SIZED TO CODE 250-102 & TABLE 250-66. 2.) USE APPROVED LUGS FOR CONDUCTOR SIZE 3.) SECURE PANEL INTERIOR.
11/19/2001 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*1.) USE APPROVED LUGS FOR WIRE SIZE 2.) FILL UNUSED OPENINGS IN DISCONNECT. 3.) NEED TO SEE FUSES. 4.) SECURE PANEL INTERIOR TO CAN.
11/15/2001 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*1.) BONDING DEVICE AT ALL SIDE OF NIPPLES AT SERVICE UNTIL 1ST DISSONNECTING MEANS. 2.) CHASE NIPPLE NOT AN APPROVED FITTING USE APPROVED FITTING. 3.) DOUBLE LUG AT METER SCOKET. 4.) COVER TO OPEN 90 5.) SECURE PANEL INTERIOR TO CAN 6.) NEED TO SEE FUSES.
11/14/2001 ELECTRIC - INTERMEDIATE Partial Approval 1.) M/C CABLE NEEDS PROTECTION WHERE PASSING AT DRYWALL RECESSED CANS INSTALLED AFTER WOOD CEILING INSTALLED WIRING COMPARTMENT IS ACCESSABLE.