Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T00CM05794
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/06/2001 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000* | |
11/28/2001 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0935*1.) BOND JUMPER TO BE SIZED TO CODE 250-102 & TABLE 250-66. 2.) USE APPROVED LUGS FOR CONDUCTOR SIZE 3.) SECURE PANEL INTERIOR. | |
11/19/2001 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0999*1.) USE APPROVED LUGS FOR WIRE SIZE 2.) FILL UNUSED OPENINGS IN DISCONNECT. 3.) NEED TO SEE FUSES. 4.) SECURE PANEL INTERIOR TO CAN. | |
11/15/2001 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0999*1.) BONDING DEVICE AT ALL SIDE OF NIPPLES AT SERVICE UNTIL 1ST DISSONNECTING MEANS. 2.) CHASE NIPPLE NOT AN APPROVED FITTING USE APPROVED FITTING. 3.) DOUBLE LUG AT METER SCOKET. 4.) COVER TO OPEN 90 5.) SECURE PANEL INTERIOR TO CAN 6.) NEED TO SEE FUSES. | |
11/14/2001 | ELECTRIC - INTERMEDIATE | Partial Approval | 1.) M/C CABLE NEEDS PROTECTION WHERE PASSING AT DRYWALL RECESSED CANS INSTALLED AFTER WOOD CEILING INSTALLED WIRING COMPARTMENT IS ACCESSABLE. |